Experiment on desiccant wheels at different regeneration temperatures.
Author(s) : HUANG Z. J., QIAN F. P., YOSHINO H. S., et al.
Summary
One of main operating parameters of desiccant wheels is the regeneration temperature. This paper presents experimental tests on performance of silica gel desiccant wheel at different temperatures. The experimental setup includes two man-made environmental chambers and a test chamber. The man-made chambers are for controlling outdoor air and indoor air conditions, and the desiccant wheels unit with a heat wheel is in the test chamber. The experimental tests carried out with outdoor air conditions of temperate and tropical climate at regeneration temperatures of 50, 55, 60, 65, 70 and 80°C. The investigation result shows that a regeneration temperature of 50°C can be used in desiccant wheels in temperate climate areas. When the regeneration temperature is over 65°C, the process air humidity is dependent on the regeneration air humidity. The latent heat to energy consumption ratio with heat wheel is 0.6-0.7 W/W, and it is twice that of without heat recovery.
Details
- Original title: Experiment on desiccant wheels at different regeneration temperatures.
- Record ID : 2009-0749
- Languages: English
- Source: Cryogenics and refrigeration. Proceedings of ICCR'2008.
- Publication date: 2008/04/05
Links
See other articles from the proceedings (170)
See the conference proceedings
Indexing
-
Performance analysis of multi-partition desicca...
- Author(s) : JEONG J., YAMAGUCHI S., SAITO K., et al.
- Date : 2008/09/07
- Languages : English
- Source: 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Formats : PDF
View record
-
Characterization of desiccant wheels with alter...
- Author(s) : WHITE S. D., GOLDSWORTHY M., REECE R., et al.
- Date : 2011/12
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 8
- Formats : PDF
View record
-
The effect of ambient temperature and humidity ...
- Author(s) : THOM M. G., SHEER T. J.
- Date : 1999/09/19
- Languages : English
- Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Formats : PDF
View record
-
Experimental analysis on the performances of a ...
- Author(s) : ANGRISANI G., MINICHIELLO F., ROSELLI C., et al.
- Date : 2011/04/06
- Languages : English
- Source: Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
View record
-
Sorptionsregenerator: Hauptbaustein des SGK-Kli...
- Author(s) : FRANZKE U.
- Date : 1999/12
- Languages : German
- Source: KI Luft Kältetech. - n. 12
View record