Experimental and theoretical study on a novel double evaporating temperature chiller applied in THICS using R32/R236fa.

Author(s) : LIU J., SHE X., ZHANG X., et al.

Type of article: Article, IJR article

Summary

A novel chiller with double evaporating temperatures is proposed in this paper, which can be applied in temperature and humidity independent control system (THICS). A zeotropic mixture R32/R236fa is selected as the refrigerant, and chilled water with two different temperatures is produced. The experimental coefficient of performance (COPexp), theoretical coefficient of performance (COPth), and second law efficiency (?) of the chiller are studied. The performance of the chiller is studied by varying the mass fraction of R32 in the R32/R236fa (W(R32)), chilled water temperature, and the flow rates of the heat transfer media (chilled water and cooling water). The results show that the high temperature chilled water (TH,out) can be at 15–18?°C, and the low temperature chilled water (TL,out) can be at 6–8?°C. When TH,out is 17?°C and TL,out is 7?°C, the maximum COPth and COPexp are 4.73 and 3.97, respectively. Second law efficiency, ?, increases to 31% as W(R32) increases from 0.3 to 0.6.

Available documents

Format PDF

Pages: 343-351

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental and theoretical study on a novel double evaporating temperature chiller applied in THICS using R32/R236fa.
  • Record ID : 30021951
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 75
  • Publication date: 2017/03
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2016.08.015

Links


See other articles in this issue (29)
See the source