Experimental energy performance of open cooling towers used under low and variable approach conditions for indirect evaporative cooling in buildings.
Author(s) : COSTELLOE B., FINN D.
Type of article: Article
Summary
The success of chilled ceilings and displacement ventilation systems as a means of sensible cooling in buildings has prompted a review of evaporative cooling technology as an effective means of generating the required cooling water. When such cooling water is generated at low approach conditions (2-5 K), at the higher temperatures required in these systems (14-18°C), very high levels of availability result. In many north western European locations the levels of availability are such that the prospect of supplanting rather than simply supplementing the refrigeration system, for sensible cooling purposes, arises. The viability of the technique, however, largely depends on achieving low approach conditions, at acceptable levels of energy performance. Hence the need to investigate the energy performance of the process. This paper presents the results of recent experimental research into: i) the achievement of low approach conditions in an evaporative cooling test rig; and ii) the energy performance of this test rig when generating cooling water, indirectly, at the temperatures required for chilled ceilings. Energy performance is presented for a range of specific conditions and typical annual efficiencies of cooling water generation are determined. Results are compared with typical energy efficiencies of conventional, vapour compression based, refrigeration systems. A significant potential for improved annual energy performance, is shown.
Details
- Original title: Experimental energy performance of open cooling towers used under low and variable approach conditions for indirect evaporative cooling in buildings.
- Record ID : 2004-2927
- Languages: English
- Source: Build. Serv. Eng. Res. Technol. - vol. 24 - n. 3
- Publication date: 2003/10
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (3)
See the source
Indexing
-
Predicting thermal performance of a closed-wed ...
- Author(s) : GAN G., RIFFAT S. B.
- Date : 1999
- Languages : English
- Source: Build. Serv. Eng. Res. Technol. - vol. 20 - n. 4
View record
-
Bug hunt.
- Author(s) : BRUNDRETT G.
- Date : 2000/12
- Languages : English
- Source: Build. Serv. J. - vol. 22 - n. 12
View record
-
Thermal comfort in chilled ceiling and displace...
- Author(s) : HODDER S. G., LOVEDAY K. C., et al.
- Date : 1998/04
- Languages : English
- Source: Energy Build. - vol. 27 - n. 2
View record
-
EFFICIENCY OF VERY SIMPLE SYSTEMS FOR DOMESTIC ...
- Author(s) : RAKHMANOV A.
- Date : 1981
- Languages : Russian
- Source: Izv. Akad. nauk Turkm. SSR, Ser. fiz-teh. him. geol. nauk - n. 2
View record
-
HIGH EFFICIENCY FILTRATION.
- Author(s) : DENNIS P. J.
- Date : 1990
- Languages : English
- Source: J. chart. Inst. Build. Serv. - vol. 12 - n. 3
View record