Experimental study on multi-split air conditioner with digital scroll compressor.
Author(s) : TU Q., DONG K. J., ZOU D., et al.
Type of article: Article
Summary
A set of 10 horse powers multi-split air conditioner with a digital scroll compressor and a standard compressor was designed. The control strategy of compressor switching and the control model of compressor output capacity were presented. The output ratio of the digital compressor was determined in the control strategy. Furthermore, in the control model of compressor output capacity, considering the pressure disturbance, a certain suction pressure range was used as the pressure control target to adjust the output capacity. Experiments show that the system ran unstably, the standard compressor frequently appeared on-off phenomenon, and some operation parameters such as the output ratio of the digital compressor, the opening of electric expansive valve (EEV), the cooling capacity and the air outlet temperature fluctuated. A new control model of the output capacity was proposed, in which the average suction pressure in an adjustment period was taken as the current pressure to regulate the output capacity. Experimental results demonstrate that the control model can be used to solve the frequent on-off phenomenon of the standard compressor and oscillation of the operation parameters, realize control accuracy of less than 0.2°C deviation of the air outlet temperature. [Reprinted with permission from Elsevier. Copyright, 2011].
Details
- Original title: Experimental study on multi-split air conditioner with digital scroll compressor.
- Record ID : 30005261
- Languages: English
- Source: Applied Thermal Engineering - vol. 31 - n. 14-15
- Publication date: 2011/10
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2011.04.010
Links
See other articles in this issue (21)
See the source
-
Numerical study on performance comparison for s...
- Author(s) : LEE T., MIN B., CHOI G.-M., et al.
- Date : 2019/08/24
- Languages : English
- Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
View record
-
Modeling of variable refrigerant flow system fo...
- Author(s) : KWON L., HWANG Y., RADERMACHER R., et al.
- Date : 2012/07/16
- Languages : English
- Source: 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
A hybrid deep forest approach for outlier detec...
- Author(s) : ZENG Y., CHEN H., XU C., CHENG Y., GONG Q.
- Date : 2020/12
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 120
- Formats : PDF
View record
-
Performance comparison between bypass cycle and...
- Author(s) : MIN B., JANG S., LEE T., et al.
- Date : 2019/11
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 107
- Formats : PDF
View record
-
Indoor unit fault detector for a multi-split VR...
- Author(s) : SHI Y., KARNG S. W., KIM S. Y.
- Date : 2014/04
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 40
- Formats : PDF
View record