Experimental study on the heat transfer characteristics of a spiral fin-tube heat exchanger with staggered tube alignment.

Author(s) : KANG T., LEE M., KIM Y., et al.

Summary

A spiral fin-tube heat exchanger is expected to have better heat transfer performance than a flat plate fin-tube heat exchanger. The objective of this study is to investigate the heat transfer characteristics of the spiral fin-tube heat exchanger with staggered tube alignment varying fin spacing and the number of tube rows under non-frosting conditions. The heat transfer performance of the fin-tube heat exchanger was inversely proportional to fin spacing. The heat transfer performance is inversely proportional to the number of tube rows but the effect of the number of tube rows become negligible as the number increased. The developed heat transfer correlation shows good agreement with measured data with a mean deviation of 4.27%.

Available documents

Format PDF

Pages: pp. 252-526

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental study on the heat transfer characteristics of a spiral fin-tube heat exchanger with staggered tube alignment.
  • Record ID : 2009-2275
  • Languages: English
  • Source: ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
  • Publication date: 2009/05/20