Numerical and experimental analysis of elliptic finned-tube heat exchangers under misted conditions.

Summary

The numerical and experimental analysis was carried out to study the thermal-hydraulic characteristics in elliptical finned-tube heat exchanger under the dry and air/water spray cooled system. Three kinds of major/minor axis ratios were examined for the elliptic finned-tube heat exchangers and the results were also compared with the corresponding circular finned-tube having the same perimeter. The numerical results for the pressure and heat transfer coefficient at various inlet frontal velocities (1-5 m/s) are shown and compared with the available experimental data. The numerical results indicated that the pressure drop of circular finned-tube heat exchanger is 3 times that of the elliptic finned-tube heat exchanger, while the heat transfer coefficient of the circular finned-tube is 1.51 times that of the elliptic finned-tube. The heat transfer coefficient per unit of pressure drop for elliptic finned-tube is 1.6-2.5 times of circular finned-tube. When the air/water spray system is applied, the heat transfer could increase up to more than 30%.

Details

  • Original title: Numerical and experimental analysis of elliptic finned-tube heat exchangers under misted conditions.
  • Record ID : 2008-2444
  • Languages: English
  • Source: Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
  • Publication date: 2007/06/10