Experiments on a vapour absorption heat transformer.

Author(s) : GEORGE J. M., MURTHY S. S.

Type of article: Article, IJR article

Summary

Tests were conducted on a 3 kilowatt heating capacity R21-DMF vapour absorption heat transformer to study the influence of operating temperature on its performance. Heat source temperature and condensing temperature were varied in the ranges 50-75 and 20-40 deg C, respectively. Heat delivery temperatures up to 85 deg C and temperature lifts up to 20 deg C were achieved. Actual COPs ranged from 0.2 to 0.35, whereas exergetic efficiencies of 0.3-0.4 could be obtained.

Available documents

Format PDF

Pages: 107-119

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experiments on a vapour absorption heat transformer.
  • Record ID : 1993-3297
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 16 - n. 2
  • Publication date: 1993/03