Feasibility study and performance evaluation of low capacity water–LiBr absorption cooling.

Author(s) : KETFI O., MERZOUK M., MERZOUK N. K., et al.

Type of article: Article, IJR article

Summary

A performance analysis was carried out on water–LiBr absorption chillers performing in the five different climate zones in Algeria. A 17.6?kW single-effect and a 16?kW double-effect commercial absorption chillers were simulated. In climate zones E1 and E2, the single-effect and double-effect chillers supplied 37% and 91%, respectively, of their nominal capacity to produce chilled water at 7?°C. In the hot climate zones E3, E4 and E5, it was not feasible for either of the chillers to produce chilled water at 7?°C. By increasing the chilled water temperature to 12?°C both absorption chillers were able to operate in climate zones E3 and E4. The single-effect chiller reached 45% of its nominal capacity in zone E3 and 33% in zone E4. The double-effect chiller delivered 80% of its nominal capacity in both climate zones. Neither of the chillers was able to operate under the thermal conditions of climate zone E5.

Available documents

Format PDF

Pages: 36-50

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Feasibility study and performance evaluation of low capacity water–LiBr absorption cooling.
  • Record ID : 30022266
  • Languages: English
  • Subject: Developing country
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 82
  • Publication date: 2017/10
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2017.07.002

Links


See other articles in this issue (42)
See the source