IIR document

Finned-tube condenser design optimisation using thermoeconomic isolation.

Summary

Using a detailed system model as a comparison, the study shows that isolating the condenser component and optimising it independently by minimizing the entropy generation in the condenser component alone, also known as thermoeconomic isolation, is a practical way to design the condenser for optimum air-conditioning system efficiency. This task is accomplished by comparing the optimum design determined by maximizing the entire system's COP, an undisputed method, with the optimum design determined by minimizing the entropy generation in the isolated condenser component, with consistent constraints used for the two methods. The choice of constraints used in the isolated model is critical and discussed in detail. The resulting optimum designs from the isolated model produced a COP within 0.62 to 1.7% of the designs found by optimising the COP using an entire system model. Additionally, a 65% reduction in computation time was achieved.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Finned-tube condenser design optimisation using thermoeconomic isolation.
  • Record ID : 2005-0906
  • Languages: English
  • Source: 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
  • Publication date: 2003/08/17

Links


See other articles from the proceedings (398)
See the conference proceedings