Heat pump efficiency improvement by discharge superheated control.

Number: pap. 2176

Author(s) : TANAWITTAYAKORN W., PHRAJUNPANICH P., SIWAPORNPHAISARN S.

Summary

This research presents how to improve the heat pump efficiency by using discharge superheat control (DSH). Normal heat pump uses suction superheat control (SSH) about 5 K. At this condition, it is an optimum condition for cooling COP but it is not the highest cooling capacity. To improve heat pump efficiency, it needs to get maximum heat from Evaporator and internal heat of compressor to discharge at condensing. This condition needs to be controlled at SSH ~ 0 K. Unfortunately normal heat pump can not be controlled at this condition because of limitation of expansion valve controlling and operating limit of some compressor. New control method under this condition, is called discharge superheat control (DSH). It uses discharge temperature for controlling refrigerant flow to get the maximum heat at Evaporator and Compressor. From the experiment with brine to water(BTW) and air to water heat pump (ATW), DSH control will lead to highest HCOP up to 25% improved, comparing to the original control method.

Available documents

Format PDF

Pages: 9 p.

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Heat pump efficiency improvement by discharge superheated control.
  • Record ID : 30006627
  • Languages: English
  • Source: 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Publication date: 2012/07/16

Links


See other articles from the proceedings (195)
See the conference proceedings