Summary
The ground heat exchangers consist of pipes buried in the soil and is used for transferring heat between the soil and the heat exchanger pipes of the ground source heat pump (GSHP). Because of the complexity of the boundary conditions, the heat conduction equation has been solved numerically using alternating direction implicit finite difference formulation. A software was developed in MATLAB environment and the effects of solution parameters on the results were investigated. An experimental study was carried out to test the validity of the model. An experimental GSHP system is installed at Yildiz Technical University Davupasa Campus on 800 m2 surface area with no special surface cover. Temperature data were collected using thermocouples buried in soil horizontally and vertically at various distances from the pipe centre and at the inlet and the outlet of the ground heat exchanger. Experimental and numerical simulation results calculated using experimental water inlet temperatures were compared. The maximum difference between the numerical results and the experimental data is 10.03%. The temperature distribution in the soil was calculated and compared with experimental data also. Both horizontal and vertical temperature profiles matched the experimental data well. Simulation results were compared with the other studies. [Reprinted with permission from Elsevier. Copyright, 2008].
Details
- Original title: Heat transfer of horizontal parallel pipe ground heat exchanger and experimental verification.
- Record ID : 2009-0829
- Languages: English
- Source: Applied Thermal Engineering - vol. 29 - n. 2-3
- Publication date: 2009/02
Links
See other articles in this issue (4)
See the source
Indexing
-
Themes:
Heat pumps techniques;
Heat transfer - Keywords: Software; Horizontal tube; Ground-water; Comparison; Calculation; Heat transfer; Ground; Heat pump; Expérimentation; Heat exchanger
-
Pompe di calore geotermiche.
- Author(s) : CARLI M. de, MANTOVAN M., PRENDIN L., et al.
- Date : 2007/03
- Languages : Italian
- Source: Cond. Aria - n. 3
View record
-
Experimental comparison of four borehole heat e...
- Author(s) : ACUÑA J., PALM B.
- Date : 2008/09/07
- Languages : English
- Source: 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Formats : PDF
View record
-
A new comparison of vertical ground heat exchan...
- Author(s) : SHONDER J. A., BAXTER V., THORNTON J.
- Date : 1999
- Languages : English
- Source: ASHRAE Transactions. 1999 Annual Meeting, Seattle, Washington + CD-ROM.
View record
-
Heat extraction tests with steel foundation pil...
- Author(s) : NAGANO K., KATSURA T., TAKEDA S., et al.
- Date : 2006/03
- Languages : Japanese
- Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 108
View record
-
Design of vertical ground heat exchangers based...
- Author(s) : WANG Y., LIU F., FU X.
- Date : 2007/09
- Languages : Chinese
- Source: HV & AC - vol. 37 - n. 202
- Formats : PDF
View record