INDUSTRIAL REFRIGERATION: REGULATION OF REFRIGERANT IN FLOODED EVAPORATORS.

Author(s) : BARMWATER P.

Type of article: Article

Summary

THE ADVANTAGES OF HIGH SIDE FLOAT CONTROL AGAINST LOW SIDE FLOAT CONTROL ARE DISCUSSED, BUT EITHER CAN BE ACCOMPLISHED USING A NEW PILOT OPERATED EXPANSION VALVE AND A CONTROLLING FLOAT WITH PROPORTIONAL AND INTEGRAL CONTROL CHARACTERISTICS THE VALVE IS OPERATED BY A HEAT MOTOR THROUGH CHANGES IN A SELF INDUCTION COIL ON THE FLOAT SYSTEM, PRODUCING A FULLY MODULATING CONTROL. D.W.H.

Details

  • Original title: INDUSTRIAL REFRIGERATION: REGULATION OF REFRIGERANT IN FLOODED EVAPORATORS.
  • Record ID : 1988-0111
  • Languages: English
  • Source: Scand. Refrig./Refrig. Air Cond. Heat Recov. - vol. 90 - n. 1.071
  • Publication date: 1987