IIR document

Investigation of a diffusion absorption chiller using a plate heat exchanger as generator.

Number: 0595

Author(s) : BRUNDER J., STERGIAROPOULOS K.

Summary

Diffusion absorption chillers (DAC) are purely heat-driven and have no mechanically moving components. They use natural refrigerants, ammonia and water. So far, DACs are used commercially as refrigerators for hotels and caravanning. This research concentrates on developing a DAC for air conditioning.
A compact generator unit consisting of a plate heat exchanger (PHX) and a vertical lift tube is used for the first time. A heating circuit supplies the heat to the generator so that any heat source can drive the machine. Due to a large heat transfer area and high heat transfer coefficients achieved by using a PHX, lower temperatures are sufficient to drive the DAC.
This paper discusses preliminary investigations on the pumping performance of the generator unit. The heat transfer in the generator is analyzed and satisfying overall heat transfer coefficients up to π‘˜π‘˜=1171π‘Šπ‘Šπ‘šπ‘šβˆ’2πΎπΎβˆ’1 were found. The maximum cooling capacity achieved by the DAC investigated is 1038π‘Šπ‘Š.

Available documents

Format PDF

Pages: 11

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Investigation of a diffusion absorption chiller using a plate heat exchanger as generator.
  • Record ID : 30031865
  • Languages: English
  • Subject: Technology
  • Source: Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
  • Publication date: 2023/08/21
  • DOI: http://dx.doi.org/10.18462/iir.icr.2023.0595

Links


See other articles from the proceedings (491)
See the conference proceedings