Low temperature district heating based on low temperature geothermal heat (30°C).

Number: No 309

Author(s) : KNEPPER S., POTHOF I., ITARD L., FERREIRA C. I.

Summary

A comparative study for a representative case district in the Netherlands with around 2500 dwellings has been executed with the purpose of identifying the best solution for a Low Temperature District Heating (LTDH) with Low Temperature Geothermal Heat (LTGH) as the main heat source. The district is presently connected to the Dutch gas network. Its heat demand and building typologies are used as departing points. The comparison is based on 3 key performances indicators (KPI’s): CO2 emissions, levelized costs of energy (LCOE) and peak electricity use. The following LTDH designs have been considered: Central heat pump and collective peak supply at 70 ⁰C / 50 ⁰C; Central heat pump and decentral peak supply at 70 ⁰C / 50 ⁰C; Decentralized heat pumps using 30 ⁰C supply temperature. Individual air source heat pumps for space heating and electric boilers for domestic hot water purposes are taken as reference. The LTDH concept with decentralized heat pumps saves 19.5 %, 16.8 % and 36 % on the CO2 emission, LCOE, and electricity use in peak load hours compared to the reference concept.

Available documents

Format PDF

Pages: 12 p.

Available

Free

Details

  • Original title: Low temperature district heating based on low temperature geothermal heat (30°C).
  • Record ID : 30030091
  • Languages: English
  • Subject: Technology
  • Source: 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
  • Publication date: 2021/08/31

Links


See other articles from the proceedings (198)
See the conference proceedings