MANAGEMENT OF CONTAMINATION IN COOLING SYSTEMS FOR SUPERCONDUCTING GENERATORS. 2. PERFORMANCE OF COMPRESSOR UNIT EQUIPPED WITH SEPARATORS.

Author(s) : YAGUCHI H.

Type of article: Article

Summary

THE IMPURITY CONCENTRATION SHOULD BE REDUCED FAR BELOW 0.1 PPM BY VOLUME FOR A RELIABLE AND STABLE OPERATION OF HELIUM REFRIGERATORS. THE IMPURE GASES ARE REMOVED BY SEPARATORS PLACED AT A ROOM TEMPERATURE AND FURTHER BY < A HIGH TEMPERATURE COLD BOX > EQUIPPED WITH A LOW TEMPERATURE ADSORPTION BED. A SCALE MODEL EXPERIMENT CLOSE TO AN ACTUAL SIZE WAS PERFORMED. THE PAPER DESCRIBES THE PERFORMANCE TESTING DATA OF THOSE SEPARATING UNITS.

Details

  • Original title: MANAGEMENT OF CONTAMINATION IN COOLING SYSTEMS FOR SUPERCONDUCTING GENERATORS. 2. PERFORMANCE OF COMPRESSOR UNIT EQUIPPED WITH SEPARATORS.
  • Record ID : 1992-0071
  • Languages: English
  • Source: Cryogenics - vol. 30
  • Publication date: 1990/09

Links


See other articles in this issue (81)