Modeling and experiments on a dedicated outdoor air system using liquid desiccant heat and mass exchangers.

Number: 2110

Author(s) : WOODS J., KOZUBAL E., LUTTIK P., FOX D., WARNER J.

Summary

Liquid desiccants can provide efficient dehumidification but have yet to see widespread adoption. Most systems studied previously use natural gas-combustion to heat and regenerate the desiccant, and a central chiller plant or cooling tower for removing the heat of absorption. Here we present modeling and experimental results on a novel packaged air conditioner integrating liquid-desiccant heat and mass exchangers with a vapor compression cycle. The packaged system does not need cold or hot water from a central plant or cooling tower and is suitable for rooftop unit air conditioners. The system uses the evaporator to cool the liquid desiccant that is absorbing moisture from the air, and the condenser to heat the liquid desiccant to regenerate it. Efficiency is improved by reducing the load on the evaporator for a given supply-air dewpoint. This paper presents the measured dehumidification efficiency for a 10-ton packaged air conditioner, focusing on dehumidifying ventilation air. The paper also presents a numerical model to predict the outlet conditions and dehumidification efficiency, which we compare with the measured data.

Available documents

Format PDF

Pages: 10 p.

Available

Free

Details

  • Original title: Modeling and experiments on a dedicated outdoor air system using liquid desiccant heat and mass exchangers.
  • Record ID : 30030468
  • Languages: English
  • Subject: Technology
  • Source: 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Publication date: 2022/07/10

Links


See other articles from the proceedings (224)
See the conference proceedings