Modeling of a flat plate membrane-distillation system for liquid desiccant regeneration in air-conditioning applications.

Author(s) : RATTNER A. S., NAGAVARAPU A. K., GARIMELLA S., et al.

Type of article: Article

Summary

A thermally driven flat plate air gap membrane distillation liquid desiccant regenerator for lithium chloride in dehumidification applications is modeled. Operating conditions and device geometry are optimized, and it is found that membrane materials have little influence on regenerator performance. It is shown that radiation heat transfer across the air gap cannot be neglected. The regenerator removes 11.4 g min-1 cm-3 of moisture with a COP of 0.372 for an inlet solution concentration of 0.38, solution flow rate of 50 ml min-1, and heated solution temperature of 135°C. This design has negligible desiccant carry-over losses and operates without a blower.

Details

  • Original title: Modeling of a flat plate membrane-distillation system for liquid desiccant regeneration in air-conditioning applications.
  • Record ID : 30003418
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 54 - n. 15-16
  • Publication date: 2011/07
  • DOI: http://dx.doi.org/10.1016/j.ijheatmasstransfer.2011.02.064

Links


See other articles in this issue (3)
See the source