Non-condensable gas in the refrigerant of air-source heat pumps: Interactions between detection features, charge level, and temperature.
Author(s) : HU Y., YUILL D. P.
Type of article: IJR article
Summary
Non-condensable gas (NC) can be introduced into a vapor compression refrigeration cycle through improper installation or service, and decrease system efficiency, increase burden on the compressor, and reduce the compressor life span. Therefore, detecting this fault early can prevent energy waste and prolong the operating life of the system. However, diagnostic methods are not widely available, and neither are methods to quantify NC amounts based on easily measured variables. Therefore, an experimental test apparatus was built to provide data to improve understanding of NC-refrigerant interactions. Two NC fault intensities (50%, 100%), each at four charge levels (70%, 80%, 100%, 120%), were tested under five different ambient temperatures (0-40°C). Dry nitrogen gas was used for the NC. The results showed that the theoretical estimation method is inaccurate. The trends of the results from experimental tests are consistent with those from theoretical calculations, but the thresholds obtained from experimental tests are larger than those from theoretical calculations. This paper explains these differences, and provides a model to quantify the NC fault intensity using easily-measured variables. The specific model is applicable to typical residential air-conditioner and heat pump systems that use R410A refrigerant, but the general findings are applicable to other refrigerants.
Available documents
Format PDF
Pages: 378-384
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Non-condensable gas in the refrigerant of air-source heat pumps: Interactions between detection features, charge level, and temperature.
- Record ID : 30031983
- Languages: English
- Subject: Technology
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 153
- Publication date: 2023/09
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2022.10.006
Links
See other articles in this issue (32)
See the source
-
Automated proactive fault isolation: a key to a...
- Author(s) : KATIPAMULA BRAMBLEY M.
- Date : 2007/06/23
- Languages : English
- Source: ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
View record
-
Electrical signature based fault classification...
- Author(s) : YUILL D., MAMMOLI A., CAUDELL T., GOMATOM P., HU Y., SHOWUNMI O.
- Date : 2022
- Languages : English
- Source: 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Automatically detecting faulty regulation in HV...
- Author(s) : VERONICA D. A.
- Date : 2013/05
- Languages : English
- Source: HVAC&R Research - vol. 19 - n. 4
View record
-
Gazy nieskraplajace sie w urzadzeniu chlodniczym.
- Author(s) : HAJDUK T., BONCA Z.
- Date : 2003
- Languages : Polish
- Source: Technika Chlodnicza i Klimatyzacyjna - vol. 10 - n. 3
View record
-
Ein Monitor für Kälteanlagen.
- Author(s) : HESSE U., SPAUSCHUS H. O.
- Date : 1996/11/20
- Languages : German
- Source: DKV-Tagungsbericht 23. 1996 Leipzig.
View record