Operation performances of water cooling VRF system.

[In Chinese. / En chinois.]

Author(s) : SONG Y., FAN R., LONG W.

Type of article: Article

Summary

Describes the experiment system design. Based on the measured data, analyses the power consumption, temperature of water entering and leaving the units and temperature difference, and obtains the energy efficiency ration, seasonal energy efficiency ratio and integrated part load value on different conditions. Experiment results show that during measurement period, the highest COP of the unit 7.3, and the average value is 3.67, the SCOP reaches 1.14, and the IPLV reaches 4.65.

Available documents

Format PDF

Pages: 128-132

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: [In Chinese. / En chinois.]
  • Record ID : 30003011
  • Languages: Chinese
  • Source: HV & AC - vol. 41 - n. 254
  • Publication date: 2011/09

Links


See other articles in this issue (15)
See the source