THE REFRIGERATION EFFICIENCY, MASS FLOWS THROUGH LP AND HP COMPRESSORS, POWER INPUT AND INTER-STAGE PRESSURES AT THE OPTIMUM THERMODYNAMIC PERFORMANCE OF THREE-STAGE SYSTEMS ARE PRESENTED GRAPHICALLY FOR R12, R22 AND R717. CORRELATIONS ARE DEVELOPED TO ACCOUNT FOR THE EFFECTS OF SUBCOOLING OF CONDENSATE AND SUPERHEATING OF VAPOUR IN THE EVAPORATOR, EACH UP TO 15 K. THE RESPECTIVE RANGES OF CONDENSING AND EVAPORATING TEMPERATURES ARE TAKEN AS 273 TO 333 K AND 273 TO 213 K.