Parametric analysis of the airflow performance of ventilators.
Author(s) : SHARPLES S., CHILENGWE N.
Summary
In this study a parametric analysis was carried out on the interaction between louvres and various perforated mesh screens. An airflow testing rig was used to examine the impact on the louvre airflow performance of the meshes. The interaction between louvre geometries and blade inclinations with meshes of different hole sizes was also investigated experimentally. Initial results indicate that at low pressure differences the small diameter (less than 5 mm) meshes were producing a discernible reduction in the airflow, but that at larger mesh diameters (15 mm) the loss was much less significant. The suitability of CFD software to predict the mesh/louvre interactions was also investigated.
Details
- Original title: Parametric analysis of the airflow performance of ventilators.
- Record ID : 2006-1979
- Languages: English
- Publication date: 2001/09/11
- Source: Source: Proc. AIVC Conf., Bath
CP 22; sess. 5; 10 p.; fig.; tabl.; 13 ref./AIVC CD n. 6.
Indexing
-
Themes:
Other air-conditioning equipment;
Comfort air conditioning - Keywords: Comparison; CFD; Measurement; Louvre; Air; Expérimentation; Flow rate; Air conditioning
-
Experimental study on the performance of capill...
- Author(s) : PARK C., KANG H., KIM Y.
- Date : 2005/08/30
- Languages : English
- Source: Commercial Refrigeration. Thermophysical Properties and Transfer Processes of Refrigerants. Proceedings of the IIR International Conferences.
- Formats : PDF
View record
-
Full representation of supply openings for indo...
- Author(s) : ZHAO B., LI X., YAN Q.
- Date : 2001/09/11
- Languages : English
View record
-
Technologies for measuring flow rates of outdoo...
- Author(s) : FISK W. J., FAULKNER D., SULLIVAN D. P.
- Date : 2005
- Languages : English
- Source: ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
View record
-
An evaluation of three commercially available t...
- Author(s) : FISK W. J., FAULKNER D., SULLIVAN D. P.
- Date : 2005
- Languages : English
- Source: ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
View record
-
Effect of the airflow rate of a ceiling type ai...
- Author(s) : NOH K. C., HAN C. W., OH M. D.
- Date : 2008/03
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
- Formats : PDF
View record