Part-load characteristics of a new ammonia/lithium nitrate absorption chiller.
Author(s) : ZAMORA M., BOUROUIS M., CORONAS A., et al.
Type of article: Article, IJR article
Summary
A pre-industrial prototype of a new water-cooled ammonia/lithium nitrate absorption chiller was characterised at part-load operation mode. The chiller was built using brazed plate heat exchangers in all its components, including the absorber and the generator.
A test campaign was carried out varying the thermal load in the chilled water circuit and keeping the hot and cooling water temperatures constant. Part-load curves of the thermal and electrical coefficients of performance were obtained, plotted and compared with data from the literature on small capacity absorption chillers with conventional working pairs, namely ammonia/water and water/lithium bromide. The experimental results showed that to achieve a higher electrical coefficient of performance at part-load operation, it was much more convenient to use an ON-OFF control than to modify the hot water temperature. Furthermore, using a simple ON-OFF control strategy, the behaviour of the new absorption chiller was more agile and responded more quickly. The part-load curve of the electrical coefficient of performance was obtained by adjusting the experimental data to the shape of the curve proposed in the standard prEN-14825:2011 for air-to-water chillers. The Cc coefficient was 0.7985 matching the value obtained dividing the remaining electrical consumption measured during the OFF half cycles by the total energy consumption generated.
Available documents
Format PDF
Pages: 43-51
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Part-load characteristics of a new ammonia/lithium nitrate absorption chiller.
- Record ID : 30014805
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 56
- Publication date: 2015/08
Links
See other articles in this issue (21)
See the source
Indexing
-
Themes:
Ammonia;
Absorption and adsorption systems - Keywords: Lithium; Control (automatic); Chiller; Ammonia; Absorption system; Prototype; Nitrate; Part load
-
Experimental results of a direct air-cooled amm...
- Author(s) : LLAMAS-GUILLÉN S. U., CUEVAS R., BEST R., et al.
- Date : 2014/06
- Languages : English
- Source: Applied Thermal Engineering - vol. 67 - n. 1-2
View record
-
Partial load performance analysis of a single e...
- Author(s) : MAGNANI S., LAGANÁ A., BRUNO J. C., et al.
- Date : 2016/05/03
- Languages : English
- Source: CYTEF 2016. VIII Congreso Ibérico y VI Congreso Iberoamericano de las Ciencias y Técnicas del Frío, Coimbra-Portugal, 3-6 mayo, 2016.
- Formats : PDF
View record
-
Ammonia-lithium nitrate absorption chiller with...
- Author(s) : VENTAS R., LECUONA A., ZACARÍAS A., et al.
- Date : 2010/08
- Languages : English
- Source: Applied Thermal Engineering - vol. 30 - n. 11-12
View record
-
Development of a small capacity air-cooled ammo...
- Author(s) : ZAMORA M., BOUROUIS M., VALLÈS M., et al.
- Date : 2011/04/06
- Languages : English
- Source: Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
View record
-
Pre-industrial development and experimental cha...
- Author(s) : ZAMORA M., BOUROUIS M., CORONAS A., et al.
- Date : 2014/09
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 45
- Formats : PDF
View record