Performance evaluation of low-GWP refrigerants in 1-100 ton scroll compressors.

Number: A3-138

Author(s) : BRADSHAW C. R.

Summary

Performance evaluation of low-GWP refrigerants in scroll compressor is carried out to aid the selection of suitable refrigerant for different applications. The open-source modeling platform PDSim, used for this study, is based on the mechanistic chamber model that has the accuracy comparable to the heuristic methods. The geometry is scaled for 1-100ton cooling capacity and is presented in a companion paper [1]. Additionally, ports and bearings are scaled to make their effect fair for a range of capacities and refrigerants. The simulation model is validated using two example scroll compressors. The predicted mass flow rate and power are within 3% MAE while the isentropic efficiency is within 4% MAE. A validated model and standard AHRI conditions are used for the performance evaluation of the refrigerants over a range of 1 to 100 tons of refrigeration capacity. Seven refrigerants are studied including low-pressure refrigerants, R1234ze(E) and R1234yf, medium-pressure refrigerants, R410A, R32, R454B, and R452B and high-pressure R744. The results suggest that an optimum range does exist for each refrigerant to achieve good compressor performance. The leakage area is the primary contributor to the scroll compressor performance.

Available documents

Format PDF

Pages: 10

Available

Free

Details

  • Original title: Performance evaluation of low-GWP refrigerants in 1-100 ton scroll compressors.
  • Record ID : 30028745
  • Languages: English
  • Subject: Technology
  • Source: 12th International Conference on Compressors and their Systems
  • Publication date: 2021/09
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (63)
See the conference proceedings