PERFORMANCE OF A TWO-PHASE THERMOSIPHON AIR-TO-AIR HEAT EXCHANGER.
Author(s) : MCDONALD T. W., KOSNIK M., BERTONI G.
Summary
THE PERFORMANCE OF AN AIR-TO-AIR, MULTIPLE-LOOP, TWO-PHASE THERMOSIPHON HEAT EXCHANGERSYSTEM, UTILIZING R11 AS ITS WORKING FLUID AND FINNED TUBE COILS AS ITS EVAPORATOR AND CONDENSER, HAS BEEN STUDIED EXPERIMENTALLY. IT WAS FOUND THAT THE EFFECTIVENESS OF THE SYSTEM WAS INSENSITIVE TO THE QUANTITY OF CHARGE IN THE EVAPORATOR, EXCEPT WHEN DRYOUT OCCURRED ; IT INCREASED WITH THE HOT TO COLD AIR DUCT TEMPERATURE DIFFERENCE AND DECREASED AS THE AIRFLOW RATES INCREASED.
Details
- Original title: PERFORMANCE OF A TWO-PHASE THERMOSIPHON AIR-TO-AIR HEAT EXCHANGER.
- Record ID : 1986-2244
- Languages: English
- Publication date: 1985
- Source: Source: ASHRAE Trans.
vol. 91; n. 2A; 209-215; 7 fig.; 6 ref. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Heat transfer
- Keywords: Heat pipe; Finned tube; Measurement; Heat transfer; Thermosyphon; Air-air; R11; Performance
-
WATER COOLER: THE FINNED TUBE.
- Author(s) : MENZE K. W., WEBB R. L., APPARAO T. R.
- Date : 1989/05
- Languages : German
- Source: Kälte + Klimatechnik (Die) - X
View record
-
ROW EFFECT FOR R11 CONDENSATION ON ENHANCED TUBES.
- Author(s) : WEBB R. L., MURAWSKI C. G.
- Date : 1990
- Languages : English
- Source: J. Heat Transf. - vol. 112 - n. 3
View record
-
EVAPORATOR PERFORMANCE OF FINNED AIR-TO-AIR TWO...
- Author(s) : MATHUR G. D., MCDONALD T. W.
- Date : 1987
- Languages : English
View record
-
FILM CONDENSATION OF R11 VAPOUR ON SINGLE HORIZ...
- Author(s) : SUKHATME S. P., JAGADISH B. S., PRABHAKARAN P.
- Date : 1990
- Languages : English
- Source: J. Heat Transf. - vol. 112 - n. 1
View record
-
BOILING ON A FINNED TUBE AND A FINNED TUBE BUNDLE.
- Author(s) : HAHNE E., MULLER J.
- Date : 1983/06
- Languages : English
- Source: International Journal of Heat and Mass Transfer - vol. 26 - n. 6
View record