IIR document
Potentiometric and economic analysis of using air and water-side economizers for data center cooling based on various weather conditions.
Author(s) : DEYMI-DASHTEBAYAZ M., NAMANLO S. V.
Type of article: Article, IJR article, Case study
Summary
In this study, a thermo-economic analysis was carried out for using Air-Side Economizer (ASE), Water-Side Economizer (WSE) and Combined Air or Water Economizer (CAWE) operation mode in order to cool a data center in ten cities of Iran with various weather conditions. The energy and cost saving potentials in Mashhad municipality's data center was studied as a case study and the findings were generalized for all cities during a year. The results showed that there are energy and cost savings potential by employing CAWE operation mode for all cities except coastal cities. In addition, the Power Usage Effectiveness (PUE) of the data center can be improved by a range from 10% to 12% using CAWE cooling mode for most cities. Finally, it was found that economic index of relative net present value (RNPV) for ASE, WSE and CAWE will be positive if their relative annual potential (RAP) are higher than 12%, 23% and 35%, respectively.
Available documents
Format PDF
Pages: 213225
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Potentiometric and economic analysis of using air and water-side economizers for data center cooling based on various weather conditions.
- Record ID : 30025504
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 99
- Publication date: 2019/03
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2019.01.011
Links
See other articles in this issue (45)
See the source
Indexing
-
Themes:
Other industrial applications;
Other air-conditioning applications - Keywords: Data centre; Fan; Cooling; Iran; Case study; Economizer
-
Cooling solutions in an operational data centre...
- Author(s) : FAKHIM B., BEHNIA M., ARMFIELD S. W., et al.
- Date : 2011/10
- Languages : English
- Source: Applied Thermal Engineering - vol. 31 - n. 14-15
View record
-
Data IV à Marcoussis : des terminaux au CO2 pou...
- Author(s) : BEAUMONT C.
- Date : 2012/01
- Languages : French
- Source: Chaud Froid Performance - n. 752
View record
-
Klimatisierung von Rechenzentren: Traumhaus für...
- Date : 2010/07
- Languages : German
- Source: KI Kälte Luft Klimatechnik - n. 7-8
View record
-
Data center retrofit: heat containment and airf...
- Author(s) : KHATTAR M. K.
- Date : 2010/12
- Languages : English
- Source: ASHRAE Journal - vol. 52 - n. 12
View record
-
Data center retrofit: heat containment and airf...
- Author(s) : KHATTAR M. K.
- Date : 2011/10
- Languages : Japanese
- Source: SHASE - vol. 85 - n. 10
View record