Prediction of on-coil temperature of condensers installed at tall building re-entrant.

Author(s) : CHOW T. T., LIN Z.

Type of article: Article

Summary

Split-type air-conditioners that serve an apartment building often have the outdoor condensing units installed at the building re-entrants. Heat energy released by the condensing units induces a hot air plume which has its temperature increase all along the path up the building. When the plume reaches the upper floors, its elevated temperature degrades the condenser efficiency and may even interrupt the air-conditioner operation because of high-temperature cut. The paper presents a modelling/computation technique to tackle this problem. An application example is quoted to demonstrate the practicability of the approach.

Details

  • Original title: Prediction of on-coil temperature of condensers installed at tall building re-entrant.
  • Record ID : 2001-0413
  • Languages: English
  • Source: Applied Thermal Engineering - vol. 19 - n. 2
  • Publication date: 1999/02

Links


See other articles in this issue (4)
See the source