IIR document
Retrofit of lower GWP alternative R449A into an existing R404A indirect supermarket refrigeration system.
Author(s) : MAKHNATCH P., MOTA BABILONI A., ROGSTAM J., et al.
Type of article: Article, IJR article
Summary
R404A is going to be phased out from most of the commercial refrigeration systems due to its high GWP value of 3943. R449A (GWP of 1282) has been proposed to replace R404A with only minor system modifications in supermarkets. This paper presents the measurements of a light retrofit replacement of R404A using R449A in a medium temperature indirect refrigeration system (secondary fluid temperature at the evaporator outlet between -9 and -4 °C). It has been demonstrated that with a slight expansion device adjustment and 4% increase of refrigerant charge, R449A can be used in this refrigeration system designed for R404A because of its suitable thermodynamic properties and acceptable maximum discharge temperature. At a secondary fluid temperature at condenser inlet of 30 °C, the COP of R449A nearly matches that of R404A (both were between 1.9 and 2.2), despite having approximately 13% lower cooling capacity. As a conclusion, attending to the GWP reduction and similar energy performance,
it was demonstrated using the TEWI methodology that the use of the recently developed refrigerant R449A in these applications can reduce the total CO2 equivalent emissions of an indirect supermarket refrigeration system designed for R404A refrigerant.
Available documents
Format PDF
Pages: 184-192
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Retrofit of lower GWP alternative R449A into an existing R404A indirect supermarket refrigeration system.
- Record ID : 30021223
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 76
- Publication date: 2017/04
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2017.02.009
Links
See other articles in this issue (33)
See the source
Indexing
-
Themes:
HFCs;
Supermarkets, display cabinets;
Blends - Keywords: Refrigerating system; R449A; R404A; Supermarket; Performance; Expérimentation; Energy saving; Retrofitting
-
Field measurements of a R404A low-temperature s...
- Author(s) : MAKHNATCH P., MOTA BABILONI A., KHODABANDEH R., et al.
- Date : 2018/04/06
- Languages : English
- Source: 5th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Beijing, Chine, 6-8 avril 2018
- Formats : PDF
View record
-
Semi-empirical analysis of HFC supermarket refr...
- Author(s) : MOTA BABILONI A., GIMÉNEZ-PRADES P., MAKHNATCH P., ROGSTAM J., FERNANDEZ MORENO A., NAVARRO-ESBRÍ J.
- Date : 2022/05
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 137
- Formats : PDF
View record
-
Application of HFO blends in new and existing c...
- Author(s) : ALLGOOD C., PANSULLA A., ROBERTS N.
- Date : 2018/09
- Languages : English
- Source: 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
View record
-
Application of HFO blends in new and existing c...
- Author(s) : ALLGOOD C.
- Date : 2018/09
- Languages : English
- Source: 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
View record
-
An evaluation of the environmental impact of di...
- Author(s) : BESHR M., AUTE V., ABDELAZIZ O., et al.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record