Selection of optimal mixed liquid desiccants and performance analysis of the liquid desiccant cooling system.

Author(s) : ZHAO X., LI X., ZHANG X.

Type of article: Article

Summary

Liquid desiccant cooling system is an energy-conservative and environment-friendly air-conditioning system. Its performance is strongly influenced by the thermal properties of liquid desiccant, especially the surface vapor pressure. Mixed liquid desiccant may have better dehumidification efficiency, lower material cost and lower energy consumption. But it is difficult to analyze its thermal properties. To improve on this, our paper proposes a method based on the NRTL equation to predict the vapor pressure of mixed liquid desiccants. Six absorbent solutions (LiBr/LiCl?+?CaCl2/MgCl2?+?water/methanol) have been analyzed, and systems employing them have also been investigated. The results show that the dehumidification efficiency of mixed liquid desiccant was higher than that of a single solution. The LiBr–CaCl2–water system can obtain higher COP compared with other systems under the condition of the same dehumidification performance in summer. Moreover, the LiCl–methanol–water may be a potential absorbent for energy saving. The results are meaningful for the selection of suitable liquid desiccants and engineering design.

Details

  • Original title: Selection of optimal mixed liquid desiccants and performance analysis of the liquid desiccant cooling system.
  • Record ID : 30017000
  • Languages: English
  • Source: Applied Thermal Engineering - vol. 94
  • Publication date: 2016/02/05
  • DOI: http://dx.doi.org/10.1016/j.applthermaleng.2015.09.037

Links


See other articles in this issue (46)
See the source