IIR document

Simplified model of a membrane-based rectangular micro-desorber for absorption chillers.

Author(s) : VENEGAS M., VEGA M. de, GARCIA-HERNANDO N., et al.

Type of article: Article, IJR article

Summary

The simulation of the heat and mass transfer in a H2O–LiBr microchannel desorber endowed with a microporous membrane is presented. The heat and mass transfer processes are modelled by means of selected correlations gathered from the open literature. The simulation provides the evolution along the channels of the parameters involved in the process: heat and mass transfer coefficients, solution concentration, temperatures of the working fluids and pressure potential. The calculated values of the desorption rate are compared to experimental data gathered from the open literature. For the case considered in this study, the maximum ratio between cooling capacity of the chiller and desorber volume is 2312?kW m-3. This value is more than one order of magnitude higher than the ones found in conventional small-size absorption cooling chillers.

Available documents

Format PDF

Pages: 108-123

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Simplified model of a membrane-based rectangular micro-desorber for absorption chillers.
  • Record ID : 30019428
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 71
  • Publication date: 2016/11

Links


See other articles in this issue (10)
See the source