Study on thermal performance of micro-channel separate heat pipe for telecommunication stations: experiment and simulation.

Author(s) : LING L., ZHANG Q., YU Y., et al.

Type of article: Article, IJR article

Summary

A micro-channel separate heat pipe (MCSHP) as a cooling device for telecommunication stations (TSs) was experimentally investigated in this work. A steady-state mathematical model was built and validated with experimental data. The cooling capacity, inlet and outlet of refrigerant temperatures and refrigerant pressure of evaporator section were measured in an enthalpy difference laboratory (EDL). The average relative errors between simulation and experiment were less than 10%. The effects of geometrical design and environment conditions on thermal performance were analyzed using the validated model. As a result of the simulations, the refrigerant side pressure drop decreased by 96.61% at the flat tube height 3.0?mm compared to 1.4?mm. And the air side pressure drop decreased by 94.49%, when fin height ranged from 4?mm to 20?mm. The cooling capacity increased by 50.65% at the fin pitch 3.0?mm compared to 1.0?mm. These factors were of practical engineering importance in optimum design of MCSHP.

Available documents

Format PDF

Pages: 198-209

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Study on thermal performance of micro-channel separate heat pipe for telecommunication stations: experiment and simulation.
  • Record ID : 30016298
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 59
  • Publication date: 2015/11

Links


See other articles in this issue (27)
See the source