System analysis on a thermal transistor for heat recovery.

Number: 0096

Author(s) : SUZUKI H., HIDEMA R., ITAYA Y., NAKASO K., KAWAMURA K.

Summary

A system analysis has been performed on the thermal transistor which can simultaneously provide both chilled water at 7°C and hot pressurized water at 120°C from the exhausted heat at 80°C.  As the absorbents, lithium bromide solution was used at the highest concentration of 64 wt%. The mass and enthalpy balances were considered in the analysis.  The distribution ratio of the water supplied from the condenser to high pressure evaporator on low pressure evaporator was changed from 0.200 to 0.800.  From the results, it was found that the enthalpy ratio of hot water to chilled water increases with the distribution ratio.  However, the coefficient of performance decreased with the distribution ratio from 0.606 to 0.461. This is because the exhausted heat to the high-pressure evaporator increases.  On the other hand, overall exergy efficiency increases with the distribution ratio and it shows 0.569 at maximum in the present condition.

Available documents

Format PDF

Pages: 9

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: System analysis on a thermal transistor for heat recovery.
  • Record ID : 30031373
  • Languages: English
  • Subject: Technology
  • Source: Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
  • Publication date: 2023/08/21
  • DOI: http://dx.doi.org/10.18462/iir.icr.2023.0096

Links


See other articles from the proceedings (491)
See the conference proceedings