The exergy analysis of the open-cycle absorption chiller.

Author(s) : LU S. K., ZHANG X. S., MA J. M.

Summary

The principle and characteristics of the open-cycle absorption chiller are introduced. The model is established for the exergy analysis of the wet air and the solution. In the hypothesis operating mode, the process design and the thermal computation are carried for the system. Then each condition parameter of the system is set. Applying the balanced equation, the exergy destruction of each part of the chiller is derived. The chiller has an exergy efficiency of 18.13%. The analysis shows that the site with the maximum losses of exergy is the regenerator. It is discussed that how to reduce the loss of the exergy in the regenerator and how to increase exergy efficiency for the system.

Available documents

Format PDF

Pages: ICR07-B2-1204

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: The exergy analysis of the open-cycle absorption chiller.
  • Record ID : 2008-0632
  • Languages: English
  • Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Publication date: 2007/08/21

Links


See other articles from the proceedings (839)
See the conference proceedings