Theoretical study on separate sensible and latent cooling air-conditioning system.

Author(s) : LING J., HWANG Y., RADERMACHER R.

Type of article: Article, IJR article

Summary

The advantage of separating sensible and latent cooling (SSLC) via the use of separate cycles is saving energy by raising the evaporating temperature of the sensible cooling process. In this study, the pertinent characteristics of the SSLC system using two parallel vapour compression cycles were investigated. The requirement for high air flow rate through the sensible evaporator was the most important hardware design issue, since it might lead to a high air-side pressure drop. To address this issue, a new air distribution method, which could significantly reduce the pressure drop, was proposed to replace the conventional one. The heat exchanger modelling results demonstrated that sensible evaporators of the SSLC system could provide the equivalent cooling capacity at reduced air-side pressure drop to that of the conventional system without increasing the total heat transfer area. Although initial investment of the SSLC system is projected to be higher than the conventional system, the estimated operating cost of the SSLC system is lower than the conventional one because of the low energy consumption.

Available documents

Format PDF

Pages: pp. 510-520

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Theoretical study on separate sensible and latent cooling air-conditioning system.
  • Record ID : 2010-0187
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 3
  • Publication date: 2010/05

Links


See other articles in this issue (21)
See the source