IIR document

A minichannel aluminium tube heat exchanger. 1. Evaluation of single-phase heat transfer coefficients by the Wilson plot method.

Author(s) : FERNANDO P., PALM B., AMEEL P., et al.

Type of article: Article, IJR article

Summary

A prototype liquid-to-refrigerant heat exchanger was developed with the aim of minimizing the refrigerant charge in small systems. To allow correct calculation of the refrigerant side heat transfer, the heat exchanger was first tested for liquid-to-liquid (water-to-water) operation in order to determine the single-phase heat transfer performance. These single-phase tests are reported in this paper. The heat exchanger was made from extruded multiport aluminium tubes and was designed similar to a shell-and-tube heat exchanger. The heat transfer areas of the shell-side and tube-side were approximately 0.82 and 0.78 m2, respectively. There were six rectangular-shaped parallel channels in a tube. The hydraulic diameter of the tube-side was 1.42 mm and of the shell-side 3.62 mm. Tests were conducted with varying water flow rates, temperature levels and heat fluxes on both the tube and shell sides at Reynolds numbers of approximately 170-6000 on the tube-side and 1000-5000 on the shell-side, respectively. The Wilson plot method was employed to investigate the heat transfer on both the shell and tube sides. In the Reynolds number range of 2300-6000, it was found that the Nusselt numbers agreed with those predicted by the Gnielinski correlation within plus or minus 5% accuracy. In the Reynolds number range of 170-1200 the Nusselt numbers gradually increased from 2.1 to 3.7. None of the previously reported correlations for laminar flow predicted the Nusselt numbers well in this range. The shell-side Nusselt numbers were found to be considerably higher than those predicted by correlations from the literature. See also this Bulletin, references 2008-1563 and 1564.

Available documents

Format PDF

Pages: 669-680

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: A minichannel aluminium tube heat exchanger. 1. Evaluation of single-phase heat transfer coefficients by the Wilson plot method.
  • Record ID : 2008-1562
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 4
  • Publication date: 2008/06

Links


See other articles in this issue (18)
See the source