A modified model to predict air infiltration into refrigerated facilities through doorways.

Author(s) : CLELAND D. J.

Summary

This paper describes a modification of the model in the ASHRAE Handbook to predict the rate of air infiltration through doors into refrigerated facilities. The model sums the contributions of air tightness (infiltration when the door is closed), air infiltration due to door openings, and the additional air exchange caused by forklift traffic through the doors. The modified model was developed based on measured air infiltration rates through rapid-roll and sliding doors (with and without strip-curtain protection) into seven refrigerated warehouses with different sizes ranging operating at different temperatures for a range of forklift movement rates.

Details

  • Original title: A modified model to predict air infiltration into refrigerated facilities through doorways.
  • Record ID : 2006-1899
  • Languages: English
  • Source: ASHRAE Transactions. 2004 Winter Meeting. Volume 110, part 1 + CD-ROM.
  • Publication date: 2004

Links


See other articles from the proceedings (19)
See the conference proceedings