EXPERIMENTAL STUDY ON AIR CURTAIN IN REFRIGERATION CHAMBERS.

[In Romanian. / En roumain.]

Author(s) : NICULITA P., PURICE N., CIOBANU A.

Type of article: Periodical article

Summary

TESTS PERFORMED IN A STORAGE ROOM SHOWED THAT FOR A TEMPERATURE DIFFERENCE OF 20 K BETWEEN EXTERNAL AIR AND STORAGE ROOM TEMPERATURES, HEAT LOSSES ARE 50,000 KCAL/H (58,000 W) AND FOR 45 K 200,000 KCAL/H (232,000 W). THE VERTICAL FLOW AIR CURTAIN WITHOUT RECYCLING CAN ENSURE A 70% REDUCTION OF HEAT LOSSES.