Summary
When an air source heat pump (ASHP) unit operates for space heating at a frosting environment, periodic defrosting is necessary to maintain a high system performance. To defrost efficiently, it is necessary to find an effective defrosting control method. In this paper, an experiment was carried out on an ASHP unit with a capillary tube as a throttle device, under simulated frosting and defrosting conditions using time control defrosting method, and the experimental results are firstly presented. Secondly, a novel defrosting control method based on the degree of refrigerant superheat (DS) is reported. To validate the novel defrosting control method, a further experiment was conducted on another ASHP unit with an electronic expansion valve (EEV) as a throttle device, under simulated frosting and defrosting conditions. The experimental results demonstrated that when applying the novel defrosting control method, defrosting was initiated before the operating performances of ASHP unit rapidly deteriorated, which was more reasonable.
Available documents
Format PDF
Pages: 2278-2288
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: A novel defrosting control method based on the degree of refrigerant superheat for air source heat pumps.
- Record ID : 30009841
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 8
- Publication date: 2013/12
Links
See other articles in this issue (37)
See the source
Indexing
-
Themes:
Heat pumps techniques;
Defrosting systems - Keywords: Control (automatic); Air-water; Air-air; Superheat; Heat pump; Expérimentation; Defrosting; Refrigerant
-
Control strategy and experimental study on a no...
- Author(s) : LIANG C. H., ZHANG X. S., LI X. W., et al.
- Date : 2010/06
- Languages : English
- Source: Applied Thermal Engineering - vol. 30 - n. 8-9
View record
-
Badania odszraniania powietrznej pompy ciepla.
- Author(s) : HRYCYK E., ZAKRZEWSKI B.
- Date : 2010/06
- Languages : Polish
- Source: Chlodnictwo - vol. 45 - n. 6
View record
-
Cross defrosting on air side heat exchanger of ...
- Author(s) : WANG Z., CHEN S., YANG C.
- Date : 2008/08
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 29 - n. 4
- Formats : PDF
View record
-
Naturumlauf-Abtauung für CO2-Luft/Wasser-Wärmep...
- Author(s) : MILDENBERGER J., KOSOWSKI K., LEMKE N., et al.
- Date : 2010/05
- Languages : German
- Source: KI Kälte Luft Klimatechnik - vol. 46 - n. 5
View record
-
Study on the operating performance of cross hot...
- Author(s) : WANG Z. Y., YANG H. X., CHEN S.
- Date : 2013/09
- Languages : English
- Source: Applied Thermal Engineering - vol. 59 - n. 1-2
View record