A STUDY OF THE OPERATING CHARACTERISTICS OF A WATER-LITHIUM BROMIDE ABSORPTION HEAT PUMP.

Author(s) : CHAUDHARI S. K.

Type of article: Article

Summary

PERFORMANCE DATA HAVE BEEN OBTAINED ON AN EXPERIMENTAL WATER-LITHIUM BROMIDE ABSORPTION HEAT PUMP CONSTRUCTED LARGELY FROM STANDARD GLASS COMPONENTS FOR THREE CONCENTRATIONS OF LITHIUM BROMIDE. THE EXPERIMENTS WHICH WERE CARRIED OUT FOR A DELIVERY TEMPERATURE OF 343 K (70 DEG C), SHOW THAT THE COP DECREASES AND THE TEMPERATURE LIFT INCREASES WITH AN INCREASE IN FLOW RATIO AND AN INCREASE IN THE CONCENTRATION OF LITHIUM BROMIDE. COP OF BETWEEN 80 AND 90% OF THE THEORETICAL MAXIMUM POSSIBLE VALUES WERE OBTAINED.

Details

  • Original title: A STUDY OF THE OPERATING CHARACTERISTICS OF A WATER-LITHIUM BROMIDE ABSORPTION HEAT PUMP.
  • Record ID : 1986-0813
  • Languages: English
  • Source: J. Heat Recov. Syst. - vol. 5 - n. 4
  • Publication date: 1985
  • Document available for consultation in the library of the IIR headquarters only.