A study of variable air volume (VAV) systems in foundries.
Author(s) : ROHDIN P., MOSHFEGH B.
Summary
The focus on implementing cost efficiency energy efficiency measures will in all probability increase in the future, but it has been shown that trustworthy, site specific information are key features is increasing the adoption of such measures. This study shows that building energy simulation software gives trustworthy predictions of energy use and average temperature in the studied case, making it possible to study different HVAC control strategies. When coupled with CFD, it is also possible to study thermal comfort, ventilation efficiency, ventilation effectiveness and draught, giving an even wider range of decision support. This study also shows that a VAV system is an interesting HVAC control technique for the studied foundry. In this case, the technical potential for reducing energy use in terms of both heat and electricity is predicted to be 30.3 and 28.9% respectively.
Details
- Original title: A study of variable air volume (VAV) systems in foundries.
- Record ID : 2008-2704
- Languages: English
- Source: Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
- Publication date: 2007/06/10
Links
See other articles from the proceedings (76)
See the conference proceedings
Indexing
- Themes: Air conditioning in laboratories and industry
- Keywords: Variable volume; Industrial application; CFD; Metallurgy; Ventilation; Factory; Design; Air; Air conditioning
-
Experiment and CFD simulation on a push-pull lo...
- Author(s) : KONDO Y., YOSHINO H., TANAKA T.
- Date : 2004/07
- Languages : Japanese
- Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 94
View record
-
Airflow control in the laboratory of the future.
- Author(s) : BERGMANS F., UIJTEWAAL H.
- Date : 1994/06
- Languages : Dutch
- Source: TVVL Mag. - vol. 23 - n. 6
View record
-
CONDITIONNEMENT D'AIR A DEBIT VARIABLE ET MAITR...
- Author(s) : VERRIER J. C.
- Date : 1986/12/01
- Languages : French
- Source: GĂ©nie clim. - n. 6
View record
-
Ventilation and air-conditioning for modern bis...
- Author(s) : HU X.
- Date : 1997/06
- Languages : Chinese
- Source: HV & AC - vol. 27 - n. 115
View record
-
Variable-air-volume retrofit of an industrial r...
- Author(s) : DOYLE D. L., BENZULY R. D., O'BRIEN J. M.
- Date : 1993
- Languages : English
- Source: ASHRAE Transactions.
View record