Active control of external volume flow rates for single effect absorption chillers.
Number: pap. n. 1287
Author(s) : PETERSEN S., HÜLS W., PAITAZOGLOU C., et al.
Summary
Energy efficient absorption chiller cooling assemblies (ACCA) ought to include active speed control of pumps and fans and heat rejection devices as well. Three external circuit pumps can be controlled actively to minimize auxiliary energy consumption. According to monitoring data of a field test with 25 absorption chillers in 16 installations, up to 80 % of auxiliary electric energy consumption is caused by the cooling water pump and the cooler. Reducing a volume flow rate by reducing fan or pump speed by 50% leads theoretically to a reduction of 87% in electricity consumption for the pump/fan. In practice within the field test, a reduction of up to 65% is attained and has been proven successfully by control of reject heat and chilled water cycle pump. Control of hot water flow has a more complex, but promising potential. Lowering e.g. hot water flow rate leads to higher set temperatures for the cooler and/or lower cooling water flow rates, thus saving electric energy.
Available documents
Format PDF
Pages: 8
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Active control of external volume flow rates for single effect absorption chillers.
- Record ID : 30026749
- Languages: English
- Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Publication date: 2019/08/24
- DOI: http://dx.doi.org/10.18462/iir.icr.2019.1287
- Notes:
Keynote
Links
See other articles from the proceedings (632)
See the conference proceedings
Indexing
-
Themes:
Chillers;
Absorption and adsorption systems - Keywords: Energy consumption; Electricity; Control (automatic); Chiller; Absorption; Pump; Testing; Flow rate
-
The power-saving effect of variable cooling wat...
- Author(s) : YOSHIDA T., YASUDA K.
- Date : 2017/08/07
- Languages : English
- Source: International sorption heat pump conference, ISHPC 2017, Tokyo august 7-10.
View record
-
Experimental analysis of a transfer function fo...
- Author(s) : GARCÍA-ARELLANO C., GARCÍA-VALLADARES O., GÓMEZ V. H.
- Date : 2010/10
- Languages : English
- Source: Applied Thermal Engineering - vol. 30 - n. 14-15
View record
-
The influences of recirculating LiBr solution i...
- Author(s) : CHIN S., JURNG J., PARK C., et al.
- Date : 2002/09/24
- Languages : English
- Source: Proceedings of the International Sorption Heat Pump Conference.
View record
-
DEVELOPMENT AND TEST ON ADVANCED EQUIPMENT FOR ...
- Author(s) : PODESSER E.
- Date : 1987/08/24
- Languages : English
- Source: Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
- Formats : PDF
View record
-
Heat transfer calculation for absorption heat p...
- Author(s) : ALBERS J., ZIEGLER F.
- Date : 2011/04/06
- Languages : English
- Source: Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
View record