An experimental investigation of a passive chilled beam system in subtropical conditions.
Author(s) : HOLE A., KOSONEN R.
Summary
Chilled beam systems are effective in providing good indoor environmental quality in an energy efficient manner. However, chilled beam systems are not common in sub-tropical climates where the requested cooling capacity is much higher than in temperate climates. This paper reports the findings of physical testing undertaken on a simulated office environment when the maximum cooling capacity was 122 W/m2. Tests were also undertaken for higher theoretical heat gains (up to 164 W/m2). The mock up test environment included a 3.6 x 3.6 m zone, representing a perimeter zone of an office building in a semi sub-tropical southern hemisphere climate. The purpose of the test was to measure the internal temperature distribution and air velocities for different heat gains and also for changes in internal layout. The test results are referenced to recognised standards for occupant comfort, particularly ISO7730. The conducted measures show that the air velocities in the occupied zone were below 0.25 m/s in all tests and the draft rates were below 20% in nearly all measured points. The location of the workplace also did not have any effect on the air velocities within the space. This shows that passive beam system, including cooled mechanical ventilation, is possible to cover the requested cooling capacity in sub-tropical conditions without any draft.
Details
- Original title: An experimental investigation of a passive chilled beam system in subtropical conditions.
- Record ID : 2008-2671
- Languages: English
- Source: Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
- Publication date: 2007/06/10
Links
See other articles from the proceedings (76)
See the conference proceedings
Indexing
-
An analysis of a flexibility chilled beam syste...
- Author(s) : KOSONEN R.
- Date : 2013/06/16
- Languages : English
- Source: Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Formats : PDF
View record
-
Study on cross-ventilation with radiation panel...
- Author(s) : SONG D., KATO S., KIM T., et al.
- Date : 2002
- Languages : English
- Source: ASHRAE Transactions. 2002 annual Meeting, Honolulu, Hawaii. Volume 108, part 2 + CD-ROM.
View record
-
Evaluation of thermal comfort and occupant sati...
- Author(s) : CAETANO D. S., KALZ D. E., LOMARDO L. L. B., et al.
- Date : 2017/06
- Languages : English
- Source: Energy Procedia - vol. 115
- Formats : PDF
View record
-
Analysis of thermal comfort in an office enviro...
- Author(s) : LEITE B. C. C., TRIBESS A.
- Date : 2006/04
- Languages : English
- Source: HVAC&R Research - vol. 12 - n. 2
View record
-
A new liquid desiccant system for air-condition...
- Author(s) : YIN Y., ZHANG X., CHEN Q.
- Date : 2008/07/14
- Languages : English
- Source: 2008 Purdue Conferences. 19th International Compressor Engineering Conference at Purdue & 12th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
View record