An experimental study of the air-side particulate fouling in the fin-and-tube heat exchangers of air conditioners.
Author(s) : AHN Y. C., KIM G. T., HWANG Y. J., et al.
Summary
An experimental study was conducted to investigate the chronological performance variation such as pressure drop across a heat exchanger and cooling capacity due to the air-side particulate fouling of fin-and-tube heat exchangers for air conditioner evaporators used. 30 samples of air conditioners used in the field such as hotels, restaurants, and offices were collected in chronologically used order. The study was intended to provide factual long-term fouling data under actual operating conditions. It was found that the important parameters to influence the fouling of heat exchangers are the concentration and size of indoor pollutants, the filter efficiency, the hydrophilicity of fin surfaces, fin spacing and the structure of fins. The pressure drop of heat exchangers increases from year to year due to the deposition of indoor pollutants larger than 1 m in size and increases up to 44% in the samples used for 7 years. Also, the air-side particulate fouling degraded the cooling capacity by 10-15% in the samples used for 7 years.
Details
- Original title: An experimental study of the air-side particulate fouling in the fin-and-tube heat exchangers of air conditioners.
- Record ID : 2007-0635
- Languages: English
- Source: ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
- Publication date: 2006/05/21
Links
See other articles from the proceedings (161)
See the conference proceedings
Indexing
-
An experimental study of the air-side particula...
- Author(s) : AHN Y. C., CHEONG S. I., JUNG Y. M., et al.
- Date : 2006/07/17
- Languages : English
- Source: 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
View record
-
Numerical simulation of dehumidifying fin-and-t...
- Author(s) : OLIET C., PÉREZ-SEGARRA C. D., DANOV S., et al.
- Date : 2007/11
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 7
- Formats : PDF
View record
-
Air-side performance evaluation of three types ...
- Author(s) : ZHANG P., HRNJAK P. S.
- Date : 2009/08
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 5
- Formats : PDF
View record
-
Performance measurement of CO2 heat exchangers.
- Author(s) : HWANG Y. H., JIN D. H., RADERMACHER R., et al.
- Date : 2005
- Languages : English
- Source: ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
View record
-
Heat exchangers for air conditioners.
- Author(s) : SHIKAZONO N.
- Date : 2000/09
- Languages : Japanese
- Source: Refrigeration - vol. 75 - n. 875
View record