IIR document

An investigation of the airside performance of the slit fin-and-tube heat exchangers.

Author(s) : WANG C. C., TAO W. H., CHANG C. J.

Type of article: Article, IJR article

Summary

The airside performance of fin-and-tube heat exchangers having slit geometry is experimentally investigated in this study. A total of 12 samples were tested and compared. Effects of fin pitch and the number of tube row were examined. The test results indicated that the heat transfer performance increase with decrease of fin pitch for N= 1. However, for N greater than or equal to 4, the effect of fin pitch on the heat transfer performance is reversed. In addition to the effect of fin pitch, the heat transfer performance decrease with increase of the number of tube row and the friction factors are relatively independent of the number of tube row. Based on the present test results and those from previous investigations, a general correlation is proposed to describe the airside performance of the slit fin configuration, the mean deviations of the proposed heat transfer and friction correlation are 5.5 and 3.8%, respectively.

Available documents

Format PDF

Pages: 595-603

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: An investigation of the airside performance of the slit fin-and-tube heat exchangers.
  • Record ID : 2000-0677
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 22 - n. 8
  • Publication date: 1999/12

Links


See other articles in this issue (5)
See the source

Indexing