Condensation of R134a on enhanced tubes.

Author(s) : CHENG W. Y., WANG C. C.

Summary

Experiments were conducted to study the heat transfer characteristics of condensate on a vertical column of horizontal enhanced tubes. Three tubes arranged in a vertical column were set in stationary vapour. In the current experiment, six distinctly different enhanced tubes, including low-fin tubes of 26, 32, and 41 fins per inch and three three-dimensional-fin tubes, were tested. In addition, a plain tube was also tested for comparison with Nusselt's theory. The working fluid used on the experiment is R134a. Average condensing heat transfer coefficients were obtained from the modified Wilson plot technique.

Details

  • Original title: Condensation of R134a on enhanced tubes.
  • Record ID : 1995-3473
  • Languages: English
  • Source: ASHRAE Transactions 1994.
  • Publication date: 1994
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (40)
See the conference proceedings