DESIGN OF A PLATE-TYPE EVAPORATOR FOR HEAT PUMPS.

Author(s) : HAUKAS H. T.

Type of article: Article, IJR article

Summary

USE OF PARTICULARLY COLD AND/OR POLLUTED WATER AS A HEAT SOURCE FOR HEAT PUMPS MAKES SPECIAL DEMANDS ON EVAPORATOR DESIGN. THE PLATE-TYPE EVAPORATOR IS PROBABLY THE MOST SUITABLE DESIGN. ON THE WATER SIDE FALLING FILM FLOW IS RECOMMENDED. UNDER SUCH CONDITIONS, HEAT TRANSFER COEFFICIENT VALUES OF UP TO 1,400 AND 1,200W/M2.K ARE REACHED IN LABORATORY TESTS, USING R22 AND R12.