DUAL-DUCT VARIABLE AIR VOLUME: DESIGN/BUILD VIEWPOINT.
Author(s) : LINFORD R. G.
Summary
THE AUTHOR HAS DESIGNED, INSTALLED, COMMISSIONED, AND MAINTAINED DUAL-DUCTVARIABLE-AIR-VOLUME SYSTEMS IN A VARIETY OF LOW-RISE AND HIGH-RISE OFFICE BUILDINGS IN CALIFORNIA. THE RELATIVELY LOW INSTALLED COSTS PLUS EASE OF ZONING AND RAPID TENANT FIT-UP HAVE MADE THIS SYSTEM THE BEST CHOICE. THE SYSTEMS HAVE ALLBEEN OF THE DUAL-FAN TYPE WITH ONE FAN FOR HEATING AND ONE FAN FOR COOLING. MOST HAVE AIR ECONOMIZERS SERVING THE COOLING SYSTEM AND 100% RECIRCULATION FOR THE HEATING SYSTEM. THE DUAL-DUCT VARIABLE-AIR-VOLUME EXTERIOR ZONE BOXES HAVE BEEN OF THE 100% SHUTOFF TYPE. THE ZONE CONTROLS HAVE BEEN MOSTLY THE PRESSURE-DEPENDENT TYPE.
Details
- Original title: DUAL-DUCT VARIABLE AIR VOLUME: DESIGN/BUILD VIEWPOINT.
- Record ID : 1988-2421
- Languages: English
- Publication date: 1987
- Source: Source: ASHRAE Trans.
vol. 93; n. 2; 1742-1748; 5 fig. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Variable volume; Office; Building; Ventilation; Design; Air; Air conditioning
-
COMPARATIVE ANALYSIS OF THE AIR CONDITIONING SY...
- Author(s) : TIEGL K., SAMBOL I.
- Date : 1989/08/01
- Languages : English
View record
-
EXPERIENCE WITH VARIABLE VOLUME AIR CONDITIONIN...
- Author(s) : RAKOCZY T.
- Date : 1982/04
- Languages : German
- Source: Gesund. Ing. - vol. 103 - n. 2
View record
-
A novel variable air volume system.
- Author(s) : SIGANTO J. J. W., NOBLE P. J.
- Date : 2005/02
- Languages : English
- Source: EcoLibrium - vol. 4 - n. 1
View record
-
HVAC SYSTEM CONTROL: BEHAVIOUR IN REALITY.
- Author(s) : LEBRUN J., NIZET J. L., PIRLET A.
- Date : 1986
- Languages : English
- Source: Build. Res. Pract./ Bâtim. int. - n. 1
View record
-
FAN ELECTRICITY CONSUMPTION FOR VARIABLE AIR VO...
- Author(s) : SPITLER J. D.
- Date : 1986
- Languages : English
View record