Dynamic simulation of a single-effect ammonia-water absorption chiller.

Author(s) : KIM B., PARK J.

Type of article: Article, IJR article

Summary

A lumped-parameter dynamic simulation of a single-effect ammonia-water absorption chiller is performed. Modelling is based on the continuity of species constituting the ammonia-water mixture and the conservation of energy for each component of the absorption chiller. Ordinary differential equations governing the response of each component and the algebraic equations describing the constitutive relation are solved in parallel by numerical integration. The model has been applied to a commercially available 10.5 kW absorption chiller to study the transients of temperature, pressure, concentration, and void fraction of each component during the start-up operation. The time constant of the absorption chiller is also investigated. The parameters considered are the bulk concentration of the ammonia-water solution, the mass of the solution filled, and the volumes of key components of the absorption chiller. In addition, the reduction of the time constant by a stepwise turn-up and turndown of the flue gas flow rate during the primary stage of start-up period is demonstrated.

Available documents

Format PDF

Pages: 535-545

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Dynamic simulation of a single-effect ammonia-water absorption chiller.
  • Record ID : 2007-0795
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 3
  • Publication date: 2007/05

Links


See other articles in this issue (16)
See the source