IIR document
Experimental analysis of R-450A and R-513A as replacements of R-134a and R-507A in a medium temperature commercial refrigeration system.
Author(s) : LLOPIS R., SÁNCHEZ D., CABELLO R., et al.
Type of article: Article, IJR article
Summary
This work presents the experimental evaluation of R-513A (GWP?=?573) and R-450A (GWP?=?547) as R-134a (GWP?=?1301) drop-in replacements and as R-507A (GWP?=?3987) retrofits in a commercial direct expansion refrigeration system for medium temperature applications (2?°C). The evaluation covered 24-hour tests using a single-stage cycle with semi-hermetic compressor, an electronic expansion valve customized for each refrigerant and a commercial vertical cabinet with doors placed inside a climatic chamber. The tests were performed at three water dissipation temperatures (23.3, 32.8 and 43.6?°C). Experimental results indicate that R-513A and R-450A can operate with R-134a plants, with increments in energy consumption between -1.6 to +1.2% for R-513A and from +1.3 to +6.8% for R-450A, whereas in comparison with R-507A, R-513A offered reductions in energy consumption between 4.4 to 8.2% and R-450A between 0 to 3.3%. The paper analyzes the modification of the operating pressures/temperatures and the energy indicators using the four refrigerants.
Available documents
Format PDF
Pages: 52-66
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Experimental analysis of R-450A and R-513A as replacements of R-134a and R-507A in a medium temperature commercial refrigeration system.
- Record ID : 30022521
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 84
- Publication date: 2017/12
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2017.08.022
Links
See other articles in this issue (26)
See the source
Indexing
-
Themes:
HFCs;
Supermarkets, display cabinets;
Blends - Keywords: R507a; R134a; Comparison; Commercial application; Drop-in; R513A; R450A; Substitute; Performance; HFO; Expérimentation
-
R450a and R513a as low-GWP substitutes of R-134...
- Author(s) : LLOPIS R., NEBOT-ANDRÉS L., CATALÁN-GIL J., et al.
- Date : 2018/06/19
- Languages : English
- Source: CYTEF 2018. IX Congreso Ibérico y VII Congreso Iberoamericano de Ciencias y Técnicas del Frío, Valencia, España, 19-21 junio 2018.
- Formats : PDF
View record
-
Energy evaluation of drop-in replacements for R...
- Author(s) : MAKHNATCH P., MOTA BABILONI A., KHODABANDEH R.
- Date : 2018/06/18
- Languages : English
- Source: 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
View record
-
Analysis of low global warming potential fluori...
- Author(s) : MOTA BABILONI A.
- Date : 2016/02/01
- Languages : English
- Formats : PDF
View record
-
Long term viability of R-513A in a stationary r...
- Author(s) : MEDINA J., HUGHES J., COOMBS R.
- Date : 2019/08/24
- Languages : English
- Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
View record
-
Laboratory evaluation of R407H for commercial r...
- Author(s) : RYDKIN I., OHKUBO S., ARIMOTO H., et al.
- Date : 2018/07/09
- Languages : English
- Source: 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record