IIR document

Experimental analysis of the R744 vapour compression rack equipped with the multi-ejector expansion work recovery module.

Author(s) : HAIDA M., BANASIAK K., SMOLKA J., et al.

Type of article: Article, IJR article

Summary

A test facility for the experimental investigation of the R744 vapour compression rack equipped with a multi-ejector expansion work recovery module was designed and manufactured. A comparison of the R744 multi-ejector refrigeration system with the R744 parallel compression system at the same test facility was carried out based on the energy performance characteristics of refrigeration capacity, power consumption, COP, and exergy efficiency. Apart from the system performance comparison, the influence of the pressure level in the flash tank on the system performance for the two alternatives was analysed. The experimental results indicate COP and exergy efficiency improvements of the multi-ejector refrigeration system up to 7% and 13.7%, respectively. The highest values of COP and exergy efficiency were obtained by a multi-ejector refrigeration system with the tank pressure lift close to the maximum value possible to operate the multi-ejector expansion module. The values of the effective compressor efficiencies were significantly different, depending on the operation module (cooling load and heat rejection conditions).

Available documents

Format PDF

Pages: 93-107

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental analysis of the R744 vapour compression rack equipped with the multi-ejector expansion work recovery module.
  • Record ID : 30017221
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 64
  • Publication date: 2016/04

Links


See other articles in this issue (16)
See the source