IIR document

Experimental investigation of the COP improvement of a refrigeration cycle by use of an ejector.

Author(s) : LUCAS C., KOEHLER J.

Type of article: Article, IJR article

Summary

In this study, an experimental comparison between the standard CO2 expansion valve refrigeration cycle and the ejector refrigeration cycle is presented. High pressure variations for different evaporation pressures and gas cooler outlet temperatures were performed. Additionally, the ejector efficiency, the entrainment ratio, and the pressure recovery by the ejector were investigated at these conditions. Both investigated cycles where realized using the same test rig, thus minimizing comparison errors. Compared to the maximal COP of the expansion valve cycle, COP improvements of the ejector cycle of 17% were reached with ejector efficiencies of up to 22%.

Available documents

Format PDF

Pages: 1595-1603

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental investigation of the COP improvement of a refrigeration cycle by use of an ejector.
  • Record ID : 30004800
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 6
  • Publication date: 2012/09

Links


See other articles in this issue (28)
See the source